Understanding Seasonal Efficiency in Heat Pumps: SEER and SCOP

In the evaluation of heat pump performance, it is crucial to move beyond instantaneous measurements to understand how a unit operates over an entire season.

While metrics like the Energy Efficiency Ratio (EER) and the Coefficient of Performance (COP) provide a snapshot of efficiency at full load under specific Eurovent conditions, seasonal values such as SEER (Seasonal Energy Efficiency Ratio) and SCOP (Seasonal Coefficient of Performance) offer a more comprehensive and realistic view. This technical article will explore the definitions of SEER for cooling and SCOP for heating, how they are calculated according to the EN 14825 standard, and why they represent a more accurate measure of real-world energy consumption.

Persea KCRA5230

1. Definition of Seasonal Efficiency According to EN 14825

The foundation for calculating seasonal efficiency is the European standard EN 14825. When examining a heat pump’s specification sheet, such as for a rooftop unit, you will find values for SEER and SCOP, often accompanied by a note referencing this standard.

The standard defines SEER as the ratio of the total annual cooling demand that the heat pump meets (measured in kilowatt-hours) to the total annual electricity consumption required to meet that demand.

SEER = Annual Cooling Demand (kWh) / Annual Energy Consumption (kWh)

Similarly, SCOP applies the same logic but for heating mode:

SCOP = Annual Heating Demand (kWh) / Annual Energy Consumption (kWh)

Essentially, these metrics represent an average EER or COP, but calculated over an entire year of operation, factoring in varying conditions rather than a single, static point. It is also important to note that these parameters refer to final energy—the electricity consumed directly from the electrical panel—as opposed to primary energy metrics (like ηs), which account for how that electricity was generated.

2. Key Factors for Calculation: Climate and Partial Load

To calculate these seasonal values, EN 14825 requires the definition of two critical environmental factors: the climate zones in which the unit will operate and its performance under partial load conditions.

2.1. Climate Zones and Operating Hours

A heat pump’s efficiency is heavily dependent on the outdoor ambient temperature. The standard defines several climate profiles, represented as histograms that show the number of hours per year a specific outdoor temperature occurs.

For heating mode, Europe is divided into three distinct climate zones, ensuring the SCOP value is relevant to the unit’s installation location:

  • Cold Zone (Helsinki): Simulates operation for 6,446 hours per year.
  • Average Zone (Strasbourg): Simulates operation for 4,910 hours per year.
  • Warm Zone (Athens): Simulates operation for 3,590 hours per year.

For cooling mode (SEER), a single, standardized climate profile is typically used. This eco-design approach ensures that a heat pump is optimized for the environment where it will be installed.

2.2. Performance at Partial Load

A heat pump rarely operates at its full capacity. For most of the year, the cooling or heating demand is lower than the unit’s maximum output. The standard accounts for this by defining specific partial load points. For example, for an air-to-air unit operating in cooling mode, four reference points are established:

  • At 35°C outdoor temperature, the unit runs at 100% load
  • At 30°C outdoor temperature, the unit runs at 74% load.
  • At 25°C outdoor temperature, the unit runs at 47% load.
  • At 20°C outdoor temperature, the unit runs at 21% load.

When these load factors are mapped onto the climate histogram, it becomes evident that the unit operates for far more hours at partial loads (e.g., at 20°C and 25°C) than it does at full load (35°C).

3. The Result: Why SEER and SCOP are Higher than EER and COP

The primary reason seasonal efficiency values are higher than their instantaneous counterparts lies in the partial load operation. The instantaneous EER and COP are measured at demanding, full-load conditions (e.g., 35°C for cooling) which, according to the climate profiles, occur for only a few hours per year.

For the vast majority of its operational time, the heat pump is effectively “oversized” for the demand. This allows it to run unloaded, with significantly greater efficiency. By averaging its high performance during these numerous partial-load hours with its performance during the few full-load hours, the resulting SEER and SCOP values provide a much higher and more accurate reflection of annual efficiency.

For instance, a rooftop unit might have an instantaneous EER of 3.25 but a seasonal SEER of 5.3. Similarly, its COP could be 3.21, while its SCOP is 4.0.

Conclusion

In summary, SEER and SCOP are fundamental metrics for accurately assessing the real-world efficiency of a heat pump. By integrating standardized climate data and performance at various partial loads, they move beyond the limitations of instantaneous ratings. These values, calculated according to EN 14825, not only allow for a fair comparison between different units but also highlight the renewable character and high performance of heat pump technology over an entire season of operation. This is crucial for making informed decisions in the design and selection of HVAC systems.